YAVV-(NAYY)
- Min. Bending radius 15xD
- Max operating temperature 70°
- Max short circuit temperature 160°
- Rated voltage Uo/U 0,6 /1 KV
- AC test voltage 3,5 KV
- Flame propagation test on single cable EN 60332-1
PVC insulated, low voltage power cables with aluminium conductor
Used as illumination cable in energy networks that there are not much mechanical compulsion in the exterior, under ground, in cable trays and watering foundations.
Rated Cross-section |
Overall Diameter of Cable |
Net Weight (Approx.) |
Conductor DC Resistance at 20C |
Current Carrying Capacity |
|
mm2 | mm | kg | ohm/km | ampere 1 | ampere 2 |
1 Core | In Ground | In Air | |||
1 x 16 | 9,3 | 120 | 1,91 | - | - |
1 x 25 | 11,5 | 174 | 1,20 | 105 | 75 |
1 x 35 | 12,7 | 213 | 0,868 | 127 | 113 |
1 x 50 | 14,6 | 277 | 0,641 | 151 | 138 |
1 x 70 | 16,1 | 355 | 0,443 | 186 | 174 |
1 x 95 | 18,7 | 476 | 0,320 | 223 | 210 |
1 x 120 | 20,4 | 568 | 0,253 | 254 | 244 |
1 x 150 | 22,5 | 697 | 0,206 | 285 | 281 |
1 x 185 | 24,9 | 847 | 0,164 | 323 | 320 |
31/2 Cores | |||||
3x16 + 1x10 | 21,0 | 635 | 1,91 | - | - |
3x25 + 1x16 | 25,0 | 868 | 1,20 | 99 | 83 |
3x35 + 1x25 | 27,6 | 1071 | 0,868 | 118 | 102 |
3x50 + 1x25 | 32,4 | 1436 | 0,641 | 142 | 124 |
3x70 + 1x35 | 36,0 | 1827 | 0,443 | 176 | 158 |
3x95 + 1x50 | 41,7 | 2436 | 0,320 | 211 | 190 |
3x120 + 1x70 | 45,9 | 3976 | 0,253 | 242 | 221 |
3x150 + 1x70 | 50,1 | 3482 | 0,206 | 270 | 252 |
3x185 + 1x95 | 56,2 | 4423 | 0,164 | 308 | 289 |
3x240 + 1x120 | 63,3 | 5612 | 0,125 | 363 | 339 |
4 Cores | |||||
4 x 16 | 21,0 | 635 | 1,91 | - | - |
4 x 25 | 26,1 | 947 | 1,20 | 99 | 83 |
4 x 35 | 29,0 | 1172 | 0,868 | 118 | 102 |
4 x 50 | 33,8 | 1572 | 0,641 | 142 | 124 |
4 x 70 | 37,8 | 2039 | 0,443 | 176 | 158 |
4 x 95 | 43,8 | 2730 | 0,320 | 211 | 190 |
4 x 120 | 47,8 | 3245 | 0,253 | 242 | 221 |
4 x 150 | 54,0 | 4165 | 0,206 | 270 | 252 |
4 x 185 | 59,7 | 5065 | 0,164 | 308 | 289 |
4 x 240 | 68,0 | 6526 | 0,125 | 363 | 339 |