NYIFY - U
- Min. Bending radius 12XD
- Max operating temperature 70°
- Max short circuit temperature 160°
- Rated voltage Uo/U 300/500 V
- AC test voltage 2 KV
- Flame propagation test on single cable EN 60332-1
.png)
PVC insulated pvc sheathed flat cables
Suitable for dry and humid areas. All type of factory, warehouse and depots where is fire and explosion threat. Not suitable for underground. Used in fixed installations laying in conduit on and under plaster.
Rated Cross-section |
Overall Diameter of Cable |
Net Weight (Approx.) |
Conductor DC Resistance at 20C |
Current Carrying Capacity |
mm2 | mm | kg | ohm/km | ampere |
In Air | ||||
2x1 | 3,3x9,6 | 44 | 18,1 | 12 |
2x1,5 | 4,4x12 | 59 | 12,1 | 19 |
2x2,5 | 5,2x13,5 | 90 | 7,41 | 25 |
2x4 | 6,3x15,5 | 127 | 4,61 | 34 |
3x1 | 3,3x10,1 | 65 | 18,1 | 12 |
3x1,5 | 4,4x19 | 89 | 12,1 | 19 |
3x2,5 | 5,2x21,5 | 135 | 7,41 | 26 |
3x4 | 6,6x25 | 191 | 4,61 | 34 |