HO7V-U
- Min. Bending radius 4xD
- Max operating temperature 70°
- Max short circuit temperature 160°
- Rated voltage Uo/U 300/500 V - 450/750 V
- AC test voltage 2 KV
- Flame propagation test on single cable EN 60332-1
pvc insulated, non-sheathed single core cables
used in closed and dry areas,switch and distribution boards,fixed installations laying in conduit on and under plaster
Rated Cross-section |
Overall Diameter of Cable |
Net Weight (Approx.) |
Conductor DC Resistance at 20C |
Current Carrying Capacity |
|
mm2 | mm | kg | ohm/km | ampere 1 | ampere 2 |
H07V-U | In Ground | In Air | |||
1,5 | 2,7 | 21 | 12,1 | 14,5 | 24 |
2,5 | 3,2 | 34 | 7,41 | 19,5 | 32 |
4 | 3,7 | 50 | 4,61 | 26 | 42 |
6 | 4,2 | 71 | 3,08 | 34 | 54 |
10 | 5,4 | 116 | 1,83 | 46 | 73 |