HO7V-K
- Min. Bending radius 6xD
- Max operating temperature 70°
- Max short circuit temperature 160°
- Rated voltage Uo/U 300/500 V - 450/750 V
- AC test voltage 2 KV
- Flame propagation test on single cable EN 60332-1
PVC insulated, single core cables with flexible copper conductor
used in closed and dry areas,switch and distribution boards, and also used for moving installations and equipments.
Rated Cross-section |
Overall Diameter of Cable |
Net Weight (Approx.) |
Conductor DC Resistance at 20C |
Current Carrying Capacity |
|
mm2 | mm | kg | ohm/km | ampere 1 | ampere 2 |
1 Core | In Ground | In Air | |||
1,5 | 2,8 | 19 | 13,3 | 14,5 | 24 |
2,5 | 3,4 | 30 | 7,98 | 19,5 | 32 |
4 | 3,9 | 44 | 4,95 | 26 | 42 |
6 | 4,4 | 63 | 3,3 | 34 | 54 |
10 | 6,1 | 112 | 1,91 | 46 | 73 |
16 | 7,4 | 169 | 1,21 | 61 | 98 |
25 | 9 | 251 | 0,78 | 80 | 129 |
35 | 10,9 | 369 | 0,554 | 99 | 158 |
50 | 12,7 | 528 | 0,386 | 119 | 198 |
70 | 14,7 | 730 | 0,272 | 151 | 245 |
150 | 21 | 1521 | 0,129 | 240 | 391 |
185 | 23,3 | 1857 | 0,106 | 273 | 448 |